FOAM NOZZLES  

Go Back


Bubblecup 1½" Flow Chart

(Metric)

 

Flow
Setting

150 Feet 200 Feet 250 Feet
20 60 95 20 60 95 20 60 95
  50 14 40 58 14 39 56 14 38 54
  75 17 49 71 17 48 69 17 47 66
  100 20 56 82 20 55 79 20 54 76
125 22 63 92 22 62 89 22 61 85
150 24 69 101 24 68 97 24 67 94
175 26 75 109 26 73 105 26 72 101
200 28 80 117 28 78 112 28 77 108
225 30 85 124 30 83 119 30 82 115
250 31 89 130 31 88 125 31 86 121

(1) Number in each box is flow in gallons per minute.
(2) Actual flows may vary with brand and condition of hose.
(3) Flows are approximate and do not account for losses in preconnect piping or changes in elevation.

Flow
Setting

150 Feet 200 Feet 250 Feet
20 60 95 20 60 95 20 60 95
  50 14 41 61 14 40 59 14 40 58
  75 17 50 75 17 49 73 17 49 71
  100 20 58 86 20 57 84 20 56 82
125 22 85 96 22 64 94 22 63 91
150 24 71 106 24 70 103 24 69 100
175 26 76 114 26 75 111 26 74 108
200 28 82 122 28 80 119 28 79 116
225 30 86 129 30 85 126 30 84 123
250 31 91 136 31 90 133 31 89 129

(1) Number in each box is flow in gallons per minute.
(2) Actual flows may vary with brand and condition of hose.
(3) Flows are approximate and do not account for losses in preconnect piping or changes in elevation.

Flow Characteristics



Back to Top