MONITORS
Distance Chart--Combination Type--100 PSI


Approximate Effective Stream Trajectory at 30° Elevation in No Wind Conditions. Distance to Last Water Drop Approximately 10% Farther

Curve A B C D E F G
US GPM 300 500 600 750 1000 1500 2000
Litres Per Min.(LPM) 1135 1893 2272 2840 3785 5678 7571
Nozzle Reaction (LBS) 152 250 303 380 505 758 1010
Nozzle Reaction (KPa) 1048 1724 2089 2620 3482 5226 6964
Distance (FEET) 178 200 210 221 238 262 280
Distance (METRE) 65 73 77 80 87 96 102
Based on nozzle pressure of 100 psi (689 KPa).
A=
Angle of Stream
P=
Total Distance
of Straight Stream
From Distant Chart
L=
Width of Stream
0=Straight Stream 100=Max. Dist. from Chart % of Straight Stream
15° 57% 7%
30° 54% 10%
60° 52% 13%
90° 43% 15%
120° 34% 17%

Back to Top
Click here to go to WFR's Home Page Copyright © WFR Wholesale Fire & Rescue Ltd.