- Suggested maximum capacity: 350'(105m) of 2½"(65mm) single
jacket cotton, rubber-lined fire hose.
- Cabinet dimensions approximately 58"(1473mm)wide x 48"(1219mm)high x 15"(380mm)deep.
NFPA 24 (1992) has a minimum standard for equipment in hose houses.
5-6.1--When hose houses are used, in addition to the hose, each shall be equipped with:
- Two approved adjustable spray-solid stream nozzles equipped with shutoffs
for each size of hose provided.
- One hydrant wrench (in addition to wrench on hydrant).
- Four coupling spanners for each size hose provided.
- Two hose coupling gaskets for each size hose.
5-6.1.1--Where two sizes of hose and nozzles are provided, reducers or
gated wyes shall be included in the hose house equipment. |